Rp.0

Characteristics

 

  • Main network voltage     400…415 V – AC at 50 Hz
  • reactive power rating     50 kvar
  • operating mode     Automatic  
  • range     VarSet  
  • device short name     VarSet automatic with detuned reactors
  • product or component type     Capacitor bank

Complementary

  • network pollution level     Polluted
  • [Gh/Sn] harmonic pollution rate     > 25…50 %
  • THDI     > 10…20 %   
  • [THDU] total harmonic distorsion     > 4…7 % 
  • tuning factor     3.8
  • tuning frequency     190 Hz 
  • step sequences     1.1.1
  • power per step     12.5 kvar
  • step composition     4×12.5
  • location of connection     Bottom
  • internal voltage transformer     400/230 V – 400 VA
  • controller type     Varlogic NR6   
  • series name     VarplusCan + detuned reactors
  • escription     poles d3P
  • capacitance tolerance     – 5 % to 10 %
  • [Ui] rated insulation voltage     690 V
  • [Uimp] rated impulse withstand voltage     8 kV
  • maximum permissible voltage     1.1 x Un (8 hours over 24 hours) conforming to IEC 60831
  • [Imp] maximum permanent current     
    Capacitor : 1.8 x In at 480 V conforming to IEC 60831
    Battery : 1.19 x In at 400…415 V conforming to IEC 61439-2
  • protection type     Without protection
  • [Icw] rated short-time withstand current     30 kA at 1 s (Icw)
  • accessibility for operation     Front
  • colour     RAL 9003 (white)
  • product weight     334 kg
  • height     1300 mm
  • width     
    Capacitor : 800 mm
    Detuned reactor : 800 mm
  • depth     300 mm   
  • provided equipment     Auxiliary transformer
  • function available     
    GenSet shedding contact
    Alarm contact

    
Environment

  • standards
    IEC 61921
    IEC 61439-2
    IEC 61439-1
  • product certifications     
    ASEFA
    CE
    EAC
  • mounting location         Indoor
  • IP degree of protection     
    Environment : IP31
    Safety : IPxx B   
  • IK degree of protection     IK10
      
  • relative humidity     <= 95 %   
  • operating altitude     <= 2000 m
     
  • ambient air temperature for operation     -5…45 °C
  • average ambient air temperature for operation     
    Annual : 35 °C
    Over 24 hours : 45 °C
VLVAF4P03506AB