Java Electrindo Incinerator CEMS Printable Report
Generated: 2026-06-04 16:52:48 WIB
Server UTC: 2026-06-04T09:52:48+00:00
Reporting window: 2026-06-04 15:52:48 WIB to 2026-06-04 16:52:48 WIB
CEMS device: INCINERATOR-CEMS-01
Scenario: NORMAL OPERATION | Status: NORMAL
Authoritative data source: TELEMETRY / SIMULATION FALLBACK
Emission Summary
| Parameter | Current | Limit | Utilization | Min | Max | Avg |
|---|---|---|---|---|---|---|
| SO2 | 99.35 mg/Nm3 | 210.00 | 47.3% | 93.01 | 114.12 | 104.03 |
| NOx | 250.45 mg/Nm3 | 470.00 | 53.3% | 241.04 | 282.39 | 262.00 |
| CO | 332.44 mg/Nm3 | 625.00 | 53.2% | 291.25 | 344.67 | 317.63 |
Enabled Modbus TCP Devices
| Device | Name | Endpoint | Unit ID | Protocol Range | Holding References | Refresh |
|---|---|---|---|---|---|---|
| DEVICE 01 | EMISSION | 192.168.1.20:502 | 1 | 0 to 24 | HR40001 to HR40025 | 5000 ms |
| DEVICE 02 | BME680 | 192.168.1.21:502 | 1 | 0 to 24 | HR40001 to HR40025 | 5000 ms |
Monitored Priority Variables
| Source | Holding Register | Label | Raw | Scaled | Unit |
|---|---|---|---|---|---|
| DEVICE-01 | HR40001 | SO2 x10 | 815 | 81.5 | mg/Nm3 |
| DEVICE-01 | HR40002 | NOx x10 | 657 | 65.7 | mg/Nm3 |
| DEVICE-01 | HR40003 | CO x10 | 6570 | 657 | mg/Nm3 |
AI-Assisted Advisory Summary
NORMAL
Incinerator CEMS is operating normally. All emissions (SO2, NOx, CO) are well below their respective limits for the past hour. Data quality is high with fresh samples and analyzer OK.
Trend interpretation
- SO2 utilization averaged 49.6% of limit, trending stable with latest at 47.3%.
- NOx utilization averaged 55.8% of limit, with latest at 53.3%, showing a slight downward trend.
- CO utilization averaged 50.9% of limit, with latest at 53.2%, indicating recent increase but still within safe range.
Recommended review actions
- Continue routine monitoring; no immediate action required.
- Monitor NOx and CO trends to ensure they remain below limits.
Priority Alarm Settings
| Device | Holding Register | Variable | LL | L | H | HH | Enabled |
|---|---|---|---|---|---|---|---|
| D01 | HR40001 | SO2 x10 | — | — | 180 | 210 | YES |
| D01 | HR40002 | NOx x10 | — | — | 350 | 400 | YES |
| D01 | HR40003 | CO x10 | — | — | 550 | 625 | YES |
Prototype CEMS report. AI output is advisory. Deterministic alarm states remain authoritative. Validate physical analyzer mapping and local compliance requirements before operational use.